Skip to content
Astera Technology

Treat a missing heartbeat as unknown rather than healthy

Apply inclusive freshness boundaries while separating monitoring absence from confirmed service failure.

Define freshness at review time

At synthetic minute 20, monitor marks heartbeat current if last received age≤5 minutes. A last received 15, B at 14, C none. A stale or absent heartbeat means observation unknown; it does not by itself prove the application is down. No transport diagnosis is supplied.

Heartbeat freshness review
ServiceLast minute /ageState
A15 /5Current
B14 /6Unknown
CNone /not computableUnknown
Download editable CSV ↓

Calculate last-observation ages

  1. Use a common review instant
  2. Calculate age only where timestamp exists
  3. Classify current or unknown

Do not convert absent timestamps to zero age.

How many services have current heartbeat evidence?

Show the worked answer

One, A; B andC are unknown. None is established as failed by this heartbeat-only worksheet.

Name unknown status precisely

Filled decision checks
CaseDecisionReason
Age exactly 5CurrentInclusive≤5 rule
No heartbeatUnknownNo received observation
Download editable CSV ↓

Use a separate application observation to resolve service state and an observation-path check to investigate missing data. Retain those two questions separately.